Whilst all efforts are made to provide accurate and timely information from the relevant source/documentation, please be aware that the information supplied may not be the most current version. The accuracy of the detail has not been confirmed by the Department and therefore should not be relied upon without first confirming the contents.

Design gaseous fire suppression systems

Design gaseous fire suppression systems

Unit of competency
National Code
PRMPFES51A
State Code
W9865
TGA Status
Deleted
DTWD Status
Deleted
Current Release Number
1.00
Current Release Date
30/03/2009
State Implementation and Classification
Approved Date
12/03/2012
Original Release Date
30/03/2009
Nominal Hours
50
Field of Education
039905 - Fire Technology
Description
This unit of competency specifies the outcomes required to design a gaseous fire suppression system and to generate design documentation and installation drawings in accordance with relevant standards, codes and regulations. All work in this area must comply with relevant legislative, industry, customer and organisational requirements, including policies and procedures relating to ozone depleting substances (ODS), synthetic greenhouse gases (SGG) and occupational health and safety (OHS).Note: RTOs must ensure candidates in this unit have appropriate background knowledge in:fluid design (hydraulic and pneumatic) relating to fire protection systemsfire chemistry (chemistry of extinguishing agents) relating to fire protection systemsphysics (force, energy, pressure, etc.) relating to fire protection systemstheory of combustionphysiology of respiration.
General notes
N/A
Elements and Performance Criteria
1 Interpret and comply with legal and industry requirements relating to gaseous fire suppression system design.
  • 1.1 Apply knowledge and understanding of legislative requirements, including the Building Code of Australia (BCA) and relevant state and territory regulations, to gaseous fire suppression system design.
  • 1.2 Apply knowledge and understanding of legislative and industry requirements to work procedures and clarify where necessary with relevant persons.
  • 1.3 Identify potential and actualbreaches of legislative and industry requirements and take action according to organisational requirements.
2 Establish system design requirements.
  • 2.1 Gather and analyse information to identify system design requirements.
  • 2.2 Perform a fire risk management assessment of the site.
  • 2.3 Document design requirements.
  • 2.4 Identify and document constraints on design.
  • 2.5 Develop suitable strategies to address identified constraints.
  • 2.6 Create appropriate records and complete design requirement documentation according to work procedures.
3 Create and quantify system design.
  • 3.1 Identify and quantify critical dimensions and system data of initial design.
  • 3.2 Create initial design based on identified design requirements and constraints.
  • 3.3 Confirm initial design is reviewed by relevant persons to check function, physical requirements and site impact.
  • 3.4 Include variations and modifications into initial design according to feedback provided.
  • 3.5 Identify documentation requirements for the initial design and associated installation processes.
  • 3.6 Prepare draft design documentation to include installationnotes, calculations and a commissioning checklist for the system.
  • 3.7 Prepare draft installation drawings to required accuracy.
  • 3.8 Calculate draft estimates of required materials, components and related costs in conjunction with other relevantpersons.
  • 3.9 Prepare bill of materials based on initial design.
  • 3.10 Evaluate initial design documentation, installation drawings and commissioning checklist against customer requirements and, where needed, quotation or tender submission requirements.
  • 3.11 Undertake initial design review with customer and document outcomes.
4 Modify and finalise system design and documentation.
  • 4.1 Modify initial design, incorporating review and evaluation feedback from customer and other relevantpersons.
  • 4.2 Test and evaluate design requirements to confirm suitability.
  • 4.3 Document modifications and test results.
  • 4.4 Review and finalise design calculations, costings and bill of materials.
  • 4.5 Complete and document final design documentation, calculations, installation drawings and commissioning checklist.
  • 4.6 Prepare 'as installed' designs and technical data schedules to customer's needs.
  • 4.7 Process final design documentation for approval and store and distribute according to organisational procedures.
  • 4.8 Create appropriate records and complete documentation according to work procedures.
RANGE STATEMENT
The range statement relates to the unit of competency as a whole. It allows for different work environments and situations that may affect performance. Bold italicised wording in the performance criteria is detailed below. Add any essential operating conditions that may be present with training and assessment depending on the work situation, needs of the candidate, accessibility of the item, and local industry and regional contexts.
Legislative requirements may include:
relevant current Australian standards, includingAS4214
relevant federal, state and territory building Acts, regulations and codes, such asOzone Protection and Synthetic Greenhouse Gas Management Act 1989
relevant international standards, including NFPA2001 and related ISO standards
fire industry codes of practice
Building Code of Australia (BCA)
building surveyor requirements, such as occupancy permits
OHS legislation, codes and regulations
dangerous goods regulations
licensing arrangements
environmental regulations, including ODS and SGG legislation, codes and regulations
other relevant legislation relating to fire protection equipment, including international, shipping and marine codes
Australian petroleum industry requirements.
Work procedures may include:
instructions from colleagues, supervisors and managers
specific customer requirements
assignment instructions
equipment manufacturer requirements
reporting and documentation requirements
ODS, SGG and OHS requirements
personal protective equipment (PPE) requirements.
Relevant persons may include:
team leaders
supervisors
managers
colleagues
customers.
Potential and actual breaches could be identified by:
direct observation
workplace quality assurance teams.
Organisational requirements may include:
legal and organisational policies and guidelines
personnel practices and guidelines outlining work roles, responsibilities and delegations
legislation relevant to the design of gaseous fire suppression systems
OHS policies, procedures and programs
procedures and work instructions to prevent the emission of ODS and SGG in the workplace
documentation and information systems and processes
use of electronic job scheduling and communication devices.
Constraints may include:
specification of works
regulatory and authority requirements
availability of components
alterations to building design.
Documentation may include:
specifications
tender designs
contract reference designs
insurance reports
bill of materials and quantities for construction design
calculations
materials listings.
Initial design may include:
system concepts
preliminary calculations.
Variations may include:
changes by other trades
changes to the structure
changes of design criteria
additional requirements by authorities.
Modifications may include:
project-specific deviations from design documents' codes and standards
specific structural constraints.
Commissioning checklist may include checking:
fire alarm is connected
type of equipment connected to fire alarm
area is fire-rated and level of rating
penetrations are properly gas-sealed
audio and visual alarms
purge ventilation system is provided
volume of room(s)
if pipework and valving was subject to hydrostatic test
if gas container storage area is covered by detection
floor tiles for under-floor detector location
operation of actuation control devices and activating mechanisms
if door release and damper release switches are fitted
visual notification at fire indicator panel
if air conditioning shutdown isolation (viaa panel zone or door switch) is operable.
Installation drawings may include:
plan views
elevation and section details
specific details
schematics
pipe construction and joining methods
operational equipment details
calculation data
details of all elements affecting the design
reference to relevant codes and standards
all detail as per relevant design standard.
Bill of materials may include:
accurate description of all materials
quantity and cost of all materials
contingency expenses.
Final design may include:
electrical, mechanical and structural design elements
'as installed' adjustments
'as installed' calculations.
EVIDENCE GUIDE
The evidence guide provides advice on assessment and must be read in conjunction with the performance criteria, required skills and knowledge, the range statement and the Assessment Guidelines for this Training Package.
Overview of assessment
Competency in this unit underpins competency in other aspects of the candidate's role in managing their work tasks.
This unit could be assessed on its own or in combination with other units of competency relevant to the job function.
Critical aspects for assessment and evidence required to demonstrate competency in this unit
A person who demonstrates competency in this unit must be able to provide evidence of:
locating, interpreting and applying relevant information, standards and specifications
creating designs for gaseous fire suppression systems based on two different gaseous extinguishing agents
complying with site safety plan, OHS regulations, ODS and SGG regulations (where required) and state and territory legislation applicable to workplace operations
complying with organisational policies and procedures, including quality requirements
communicating and working effectively and safely with others
in a minimum of two different settings:
identifying legal and industry requirements that apply to system design
analysing system design requirements
identifying and confirming system and site measurements, critical dimensions and system data
identifying risk requirements
identifying constraints to system design
developing strategies to address identified constraints

identifying and selecting appropriate products, extinguishing agents, hardware and components for use in system design
incorporating variations and modifications into system design
completing system design calculations
drafting system design drawings
preparing bill of materials for system design
identifying installation and commissioning procedures for system design
identifying safety procedures to be followed during installation and commissioning procedures
creating installation and commissioning documentation for system and components, pipes, fittings, actuation control devices, activating mechanisms and auxiliary shutdown interface, as required.
Specific resources for assessment
Resource implications for assessment include access to:
actual or simulated work environment, including gaseous fire suppression system software
customer specifications, tender or quotation documentation, and installation and maintenance requirements for a gaseous fire suppression system design
assessment documentation, including training and assessment record books
all necessary tools, specialist equipment, materials and spare parts
relevant manuals and other documentation, including Australian standards.
Where applicable, physical resources should include equipment modified for people with disabilities.
Access must be provided to appropriate learning and/or assessment support when required.
Assessment processes and techniques must be culturally appropriate, and appropriate to the oracy, language and literacy capacity of the candidate and the work being performed.
Context of assessment
For valid and reliable assessment of this unit, competency should be demonstrated over a period of time and be observed by the assessor (or assessment team working together to conduct the assessment).
Competency is to be demonstrated in a range of situations, reflecting the practical requirements of the workplace which may include customer and workplace interruptions and involvement in related activities normally experienced in the workplace.
Assessment of competency over the full range of performance criteria may be made through practical demonstrations in the work place. Consideration should be given to assessing consistency of outcome over an appropriate period of time.
Candidates should also be given the opportunity to practise and undertake self-assessment of performance before requesting formal assessment.
All safety requirements must be adhered to during all practical activities.
Oral questioning or a written assessment may be used to assess underpinning knowledge. (In assessment situations, where the candidate is offered a preference between oral questioning and written assessment, questions are to be identical.)
Assessment of evidence should establish the candidate's ability to perform the job to the standard required in the workplace.
Supplementary evidence may be obtained from relevant authenticated correspondence or reports from supervisors or team leaders that demonstrate an understanding of the requirements for gaseous fire suppression system design.
Candidate should be encouraged to compile a portfolio of examples of completed documentation relevant to the candidate's organisation. One accurate example of each completed document is suggested as sufficient to infer competency and ability to transfer appropriate skills to each document type when required in the workplace. (Oral questioning may contribute as evidence of this ability.)
Information derived from enterprise policies and practices must be treated as commercial-in-confidence.
In all cases where practical assessment is used it will be combined with targeted questioning to assess the underpinning knowledge.

Questioning will be undertaken in such a manner as is appropriate to the oracy, language and literacy levels of the candidate and any cultural issues that may affect responses to the questions. It will reflect requirements of the unit of competency and the work being performed.
Where assessment is for the purpose of recognition (RCC or RPL), the evidence provided will need to be authenticated and show that it represents current competency demonstrated over a period of time.
Performance and assessment of this unit must be carried out within the relevant requirements of the following legislative and industry framework:
building Acts, regulations and codes
Australian and international standards identified as relevant to gaseous fire suppression design
environmental regulations
manufacturer specifications
organisational requirements, including policies and procedures relating to ODS, SGG and OHS
OHS legislation, codes and regulations
ODS and SGG legislation, codes and regulations.