Whilst all efforts are made to provide accurate and timely information from the relevant source/documentation, please be aware that the information supplied may not be the most current version. The accuracy of the detail has not been confirmed by the Department and therefore should not be relied upon without first confirming the contents.
Inspect and test fire hydrant systems
Inspect and test fire hydrant systems
Unit of competency
National Code
CPPFES2037A
CPPFES2037A
State Code
WC145
WC145
TGA Status
Replaced
Replaced
DTWD Status
Transition (Replaced)
Transition (Replaced)
State Implementation and Classification
Approved Date
21/05/2012
Field of Education
039905 - Fire Technology
Original Release Date
21/05/2012
Nominal Hours
20
Description
This unit of competency specifies the outcomes required to complete six-monthly and yearly inspections and test procedures to verify that hydrant systems function as intended. The unit involves working safely, conducting compliance tests, visually inspecting, identifying non-compliance defects, fulfilling mandatory reporting requirements, as well as isolating and resetting the hydrant system.
Notes
Elements and Performance Criteria
1 Apply rules and regulations to service operations.
- 1.1 Requirements of relevant rules and regulations are confirmed and applied to work procedures.
- 1.2 Compliance requirements are checked and action is taken according to organisational policies and procedures.
2 Inspect fire hydrant system.
- 2.1 Work permits are obtained prior to entering customer premises.
- 2.2 Fire hydrant system is inspected according to inspection schedule of relevant Australian standard and customer requirements.
- 2.3 Defects are reported according to work procedures and technical specifications.
- 2.4 Potential and actual impediments to performance of fire hydrant system are identified and reported.
- 2.5 Documentation is completed and distributed according to organisational requirements.
3 Conduct testing and record results.
- 3.1 Pumpset and other system interfaces to be isolated are identified, to enable testing activity according to legislative and industry requirements.
- 3.2 Test methods are implemented according to legislative and industry requirements.
- 3.3 Routine six-monthly and yearly testing procedures are conducted to verify that system functions according to legislative and industry requirements.
- 3.4 Test results are compared with legislative and industry requirements.
- 3.5 Results are documented according to legislative and industry requirements.
- 3.6 Report is prepared and forwarded to relevant persons for action according to legislative and industry requirements.
- 3.7 System is reinstated to full operational condition according to organisational requirements.
The range statement relates to the unit of competency as a whole. It allows for different work environments and situations that may affect performance. Bold italicised wording, if used in the performance criteria, is detailed below. Essential operating conditions that may be present with training and assessment (depending on the work situation, needs of the candidate, accessibility of the item, and local industry and regional contexts) may also be included.
Rules and regulations may include:
environmental regulations
OHS legislation, codes and regulations
relevant commonwealth and state or territory building Acts, regulations, and codes, such as Building Code of Australia (BCA)
relevant Australian standards, such as:
AS 1851 Maintenance of fire protection systems and equipment
note: Australian standards are frequently revised and users must always check for currency and amendments
other relevant legislation relating to fire protection equipment, including:
international shipping codes
marine codes for different Australian States.
Requirements may be confirmed with:
colleagues
managers
supervisors
team leaders.
Work procedures may include:
assignment instructions
equipment manufacturers’ requirements
instructions from colleagues, supervisor or manager
personal protective equipment requirements
reporting and documentation requirements
specific customer requirements.
Checking system or equipment compliance requirements may include:
applying inspection, test and survey requirements according to Australian standards
reviewing documentation to verify that installed systems comply with relevant rules and regulations.
Action may include:
advising customer
documenting non-compliance
making equipment safe
reporting, as required.
Organisational policies and procedures may include:
job scheduling systems and communication devices
personnel practices and guidelines outlining work roles, responsibilities and delegations
recording and reporting documentation and systems
relevant OHS policies, procedures and programs
relevant rules and regulations
standard operating procedures, work instructions and manuals.
Fire hydrant systems include:
privately owned independent systems designed and installed for use by emergency personnel for fighting purposes, and:
designed, installed and commissioned to a ministerial specification or Australian standard, such as AS 2419 Fire hydrant installations
not forming part of a combined water-based fire-suppression system, as defined in AS 2118 Automatic fire sprinkler systems
not forming part of town’s main reticulated water supply.
Customer requirements may include:
confirming or varying service instructions
following sign-in and sign-out procedures for entry to or exit from premises
providing non-routine or urgent services
providing routine services
providing written or verbal confirmation of services provided and future maintenance schedule
sighting work permits.
Documentation may include:
application for credit forms
certificates of inspection
corrective action reports
customer recommendation forms
equipment recommendation forms
expense claims
job cards
motor vehicle fleet cards
maintenance record system
petty cash vouchers
product documentation
service agreements.
Rules and regulations may include:
environmental regulations
OHS legislation, codes and regulations
relevant commonwealth and state or territory building Acts, regulations, and codes, such as Building Code of Australia (BCA)
relevant Australian standards, such as:
AS 1851 Maintenance of fire protection systems and equipment
note: Australian standards are frequently revised and users must always check for currency and amendments
other relevant legislation relating to fire protection equipment, including:
international shipping codes
marine codes for different Australian States.
Requirements may be confirmed with:
colleagues
managers
supervisors
team leaders.
Work procedures may include:
assignment instructions
equipment manufacturers’ requirements
instructions from colleagues, supervisor or manager
personal protective equipment requirements
reporting and documentation requirements
specific customer requirements.
Checking system or equipment compliance requirements may include:
applying inspection, test and survey requirements according to Australian standards
reviewing documentation to verify that installed systems comply with relevant rules and regulations.
Action may include:
advising customer
documenting non-compliance
making equipment safe
reporting, as required.
Organisational policies and procedures may include:
job scheduling systems and communication devices
personnel practices and guidelines outlining work roles, responsibilities and delegations
recording and reporting documentation and systems
relevant OHS policies, procedures and programs
relevant rules and regulations
standard operating procedures, work instructions and manuals.
Fire hydrant systems include:
privately owned independent systems designed and installed for use by emergency personnel for fighting purposes, and:
designed, installed and commissioned to a ministerial specification or Australian standard, such as AS 2419 Fire hydrant installations
not forming part of a combined water-based fire-suppression system, as defined in AS 2118 Automatic fire sprinkler systems
not forming part of town’s main reticulated water supply.
Customer requirements may include:
confirming or varying service instructions
following sign-in and sign-out procedures for entry to or exit from premises
providing non-routine or urgent services
providing routine services
providing written or verbal confirmation of services provided and future maintenance schedule
sighting work permits.
Documentation may include:
application for credit forms
certificates of inspection
corrective action reports
customer recommendation forms
equipment recommendation forms
expense claims
job cards
motor vehicle fleet cards
maintenance record system
petty cash vouchers
product documentation
service agreements.
The evidence guide provides advice on assessment and must be read in conjunction with the performance criteria, required skills and knowledge, range statement and the Assessment Guidelines for the Training Package.
Overview of assessment
This unit of competency could be assessed by observation of practical demonstration of inspecting and testing specified fire hydrant systems.
Critical aspects for assessment and evidence required to demonstrate competency in this unit
A person who demonstrates competency in this unit must be able to provide evidence of the required skills and knowledge specified in this unit.
In particular the person should demonstrate the ability to conduct inspection and testing tasks specified in the six-monthly and yearly schedule of AS 1851 (Section 4), excluding:
inspection and testing functions associated with pressure-reducing equipment in high rise buildings, fire pumpset systems or water supply tanks
water supply proving tests.
Context of and specific resources for assessment
Assessment of essential underpinning knowledge may be conducted in an off-site context. It is to comply with relevant regulatory or Australian standards’ requirements.
Resource implications for assessment include:
operational hydrant system
adequate water supply and draining or recycling arrangements to operate hydrant system
pictures or cut-away sections of control assemblies and valves to show operation
necessary tools, specialist equipment, manuals and relevant documentation.
Method of assessment
Assessment methods must:
satisfy the endorsed Assessment Guidelines of the Property Services Training Package
include direct observation of tasks in real or simulated work conditions, with questioning to confirm the ability to consistently identify and correctly interpret the essential underpinning knowledge required for practical application
reinforce the integration of employability skills with workplace tasks and job roles
confirm that competency is verified and able to be transferred to other circumstances and environments.
Guidance information for assessment
Reasonable adjustments for people with disabilities must be made to assessment processes where required. This could include access to modified equipment and other physical resources, and the provision of appropriate assessment support.
Assessment processes and techniques should as far as is practical take into account the language, literacy and numeracy capacity of the candidate in relation to the competency being assessed.
This unit could be assessed on its own or in combination with other units relevant to the job function, for example:
CPPFES2030A Conduct basic functional testing of water-based fire-suppression systems
CPPFES2031A Inspect and test fire pumpsets
CPPFES3033A Conduct annual functional testing of complex water-based fire-suppression systems
CPPFES3034A Conduct functional water flow testing.
Overview of assessment
This unit of competency could be assessed by observation of practical demonstration of inspecting and testing specified fire hydrant systems.
Critical aspects for assessment and evidence required to demonstrate competency in this unit
A person who demonstrates competency in this unit must be able to provide evidence of the required skills and knowledge specified in this unit.
In particular the person should demonstrate the ability to conduct inspection and testing tasks specified in the six-monthly and yearly schedule of AS 1851 (Section 4), excluding:
inspection and testing functions associated with pressure-reducing equipment in high rise buildings, fire pumpset systems or water supply tanks
water supply proving tests.
Context of and specific resources for assessment
Assessment of essential underpinning knowledge may be conducted in an off-site context. It is to comply with relevant regulatory or Australian standards’ requirements.
Resource implications for assessment include:
operational hydrant system
adequate water supply and draining or recycling arrangements to operate hydrant system
pictures or cut-away sections of control assemblies and valves to show operation
necessary tools, specialist equipment, manuals and relevant documentation.
Method of assessment
Assessment methods must:
satisfy the endorsed Assessment Guidelines of the Property Services Training Package
include direct observation of tasks in real or simulated work conditions, with questioning to confirm the ability to consistently identify and correctly interpret the essential underpinning knowledge required for practical application
reinforce the integration of employability skills with workplace tasks and job roles
confirm that competency is verified and able to be transferred to other circumstances and environments.
Guidance information for assessment
Reasonable adjustments for people with disabilities must be made to assessment processes where required. This could include access to modified equipment and other physical resources, and the provision of appropriate assessment support.
Assessment processes and techniques should as far as is practical take into account the language, literacy and numeracy capacity of the candidate in relation to the competency being assessed.
This unit could be assessed on its own or in combination with other units relevant to the job function, for example:
CPPFES2030A Conduct basic functional testing of water-based fire-suppression systems
CPPFES2031A Inspect and test fire pumpsets
CPPFES3033A Conduct annual functional testing of complex water-based fire-suppression systems
CPPFES3034A Conduct functional water flow testing.
Replaces
| State Code | National Code | Title | Type |
|---|---|---|---|
| S4467 | PRMPFES37A | Inspect and maintain fire hydrants | Unit of competency |
Replaced By
| State Code | National Code | Title | Type |
|---|---|---|---|
| OCW12 | CPPFES2037 | Inspect and test fire hydrant systems | Unit of competency |
| State Code | National Code | Title | Type |
|---|---|---|---|
| D761 | CPP20511 | Certificate II in Fire Protection Inspection and Testing | Qualification |