Whilst all efforts are made to provide accurate and timely information from the relevant source/documentation, please be aware that the information supplied may not be the most current version. The accuracy of the detail has not been confirmed by the Department and therefore should not be relied upon without first confirming the contents.

Install gaseous agent containers and actuators

Install gaseous agent containers and actuators

Unit of competency
National Code
CPPFES3045A
State Code
WC158
TGA Status
Replaced
DTWD Status
Transition (Replaced)
Current Release Number
1.00
Current Release Date
10/01/2012
State Implementation and Classification
Approved Date
21/05/2012
Field of Education
039905 - Fire Technology
Original Release Date
21/05/2012
Nominal Hours
45
Description
This unit of competency specifies the outcomes required to receive and install gaseous agent containers, manifold connections, actuators and activating mechanisms.
Notes
Elements and Performance Criteria
1 Apply rules and regulations to installation operations.
  • 1.1 Requirements of relevant rules and regulations are confirmed and applied to work procedures.
  • 1.2 Compliance requirements are checked and action is taken according to ODS, SGG requirements and organisational policies and procedures.
2 Receive system components.
  • 2.1 Procurement details and specifications of system components and materials are checked against finalised design documentation and installation drawings.
  • 2.2 Pre-tested or prefabricated components are checked to ensure they have correct documentation identifying compliance with Australian standards.
  • 2.3 Components and materials are checked to confirm that they are in acceptable condition and meet quality control checks.
  • 2.4 Labour, tools, equipment and materials, and hardware components are assembled at work site.
3 Prepare for installation of gaseous agent containers and actuators.
  • 3.1 Work permits are organised prior to entering customer premises.
  • 3.2 Safety procedures are followed according to organisational, manufacturer and customer requirements.
  • 3.3 Potential hazards and risks are identified.
  • 3.4 Required tools, equipment and materials are identified, selected and checked, and used safely and efficiently.
  • 3.5 Cylinders are checked to ensure that they contain correct quantity of extinguishing agent according to specifications in installation documentation.
  • 3.6 Installation site is confirmed as appropriate with relevant persons and on finalised design documentation and installation drawings.
  • 3.7 Safety measures are confirmed to be in place prior to the installation process.
4 Install gaseous agent containers and actuators.
  • 4.1 Support systems, components and fittings are fixed according to finalised design documentation and installation drawings.
  • 4.2 Containers are supported correctly and support frame is fixed according to installation drawings.
  • 4.3 Container manifold and connection components are installed.
  • 4.4 Transport caps, discharge outlet and actuator plugs or caps and locking devices are removed according to manufacturer and organisational requirements.
  • 4.5 Flexible hose connections are physically checked for tightness and absence of kinks.
  • 4.6 Actuators are checked to ensure that they are in reset position prior to installation according to manufacturers’ requirements.
  • 4.7 Manual and pneumatic actuators, pilot and slave tubes and fittings are safely installed.
  • 4.8 Auxiliary shutdown fire system and equipment interface and alarm device connections are installed.
  • 4.9 Pilot and slave tube connections are checked for tightness and absence of kinks.
  • 4.10 Actuators are set to operate.
5 Complete installation.
  • 5.1 Installation site is left clean and tidy with materials disposed of or recycled according to state or territory legislative and industry requirements.
  • 5.2 Documentation is completed according to work procedures.
The range statement relates to the unit of competency as a whole. It allows for different work environments and situations that may affect performance. Bold italicised wording, if used in the performance criteria, is detailed below. Essential operating conditions that may be present with training and assessment (depending on the work situation, needs of the candidate, accessibility of the item, and local industry and regional contexts) may also be included.
Rules and regulations may include:
building surveyor requirements
dangerous goods regulations
environmental regulations, including ODS and SGG legislation, codes and regulations
licensing arrangements
OHS legislation, codes and regulations
relevant Australian and international standards, such as:
AS 4214 Gaseous fire extinguishing systems
ISO 14520 Gaseous fire-extinguishing systems - Physical properties and system design
NFPA 12 Standard on Carbon Dioxide Extinguishing Systems (US)
NFPA 12A Standard on Halon 1301 Fire Extinguishing Systems (US)
NFPA 2001 Standard on Clean Agent Fire Extinguishing Systems (US)
note: Australian standards are frequently revised and users must always check for currency and amendments
relevant federal, state and territory building Acts, regulations and codes, such as:
Ozone Protection and Synthetic Greenhouse Gas Management Act 1989
BCA
other relevant legislation relating to fire protection equipment, including:
international shipping codes
marine codes for different Australian States.
Requirements may be confirmed with:
colleagues
managers
supervisors
team leaders.
Work procedures may include:
assignment instructions
equipment manufacturers’ requirements
instructions from colleagues, supervisors and managers
ODS, SGG and OHS requirements
personal protective equipment (PPE) requirements
reporting and documentation requirements
specific customer requirements.
Checking compliance requirements may include:
undertaking commissioning tests detailed in Australian standards and manufacturers’ documentation to verify performance of an installed, repaired or altered piece of equipment or system
reviewing documentation to ensure containers and actuators have been installed correctly and according to the system design.
Action may include:
advising customer
documenting non-compliance
making equipment safe
reporting, as required.
ODS and SGG extinguishing agents may include:


Note list format:
product name (other names) use

Check the latest amendments to the Ozone Protection and Synthetic Greenhouse Gas Management Act for the current list of ODS and SGG extinguishing agents.
ODS and SGG extinguishing agents commonly used in Australia:
FM200 (FE-227 Heptafluoropropane, HFC-227ea) used as a total flooding extinguishing agent and as a replacement for Halon 1301
Halon 1211 (BCF, Halon 1211 BCF, Bromochlorodifluoromethane) used as a streaming agent - requires a special permit in Australia
Halon 1301 (BTM, Halon 1301 BTM, Bromotrifluoromethane) used as a total flooding agent - requires a special permit in Australia
NAF-P-III (HCFC Blend C) used as a streaming agent
NAF-P-IV (HCFC Blend E) used as a streaming agent
NAF-S-III (HCFC Blend A) used as a total flooding agent
SF6 (Sulfurhexafluoride) used as an inerting agent in sealed high voltage switchgear
ODS and SGG extinguishing agents not commonly used in Australia:
Blitz III (HCFC Blend D) used in flooding systems
CFC-11 (Trichlorofluoromethane) may be found as a propellant in some powder fire extinguishers (this product is banned in Australia but may be found on incoming foreign vessels)
FC-2-1-8 (CEA-308) used in flooding systems
FC-3-1-10 (CEA-410) used in flooding systems
FC-5-1-14 (CEA-614) used as a streaming agent
FE-13 (Trifluoromethane, HFC-23) used as a total flooding agent
FE-241 (Chlorotetrafluoroethane, HCFC-124) used as a total flooding agent for non-occupied spaces and as a streaming agent
FE-25 (Pentafluoroethane, HFC-125) used in inerting and explosion suppression applications
FE-36 (Hexafluoropropane, HFC-236fa) used in portable fire extinguishers - is a replacement for Halon 1211 and Halon 1301
FM100 (HBFC-22B1) used in portable fire extinguishers
Halon 2402 (Dibromotetrafluoroethane) limited use in military systems - requires a special permit in Australia
Halotron I (HCFC Blend B or HCFC-123) used as a total flooding agent and streaming agent
Halotron II (blend of HFC-143a and HFC-125) used as a total flooding agent and as a replacement for Halon 1301
HCFC-22 (Chlorodifluoromethane) used as a propellant in some powder fire extinguishers (this product is banned in Australia but may be found on incoming foreign vessels)
HFC-134a (Unsymmetric tetrafluoroethane) used as a propellant in some powder fire extinguishers.
Organisational policies and procedures may include:
job scheduling systems and communication devices
personnel practices and guidelines outlining work roles, responsibilities and delegations
procedures and work instructions to prevent the emission of ODS and SGG in the workplace
recording and reporting documentation and systems
relevant OHS policies, procedures and programs
relevant rules and regulations
standard operating procedures, work instructions and manuals.
System components and materials may include:
actuators (pneumatic, electrical, mechanical and manual operation)
agent discharge nozzles
agent distribution pipework and hose networks
container bank manifold connections
container discharge valves
control equipment
detection devices
extinguishing agent containers, such as tanks and cylinders
flexible discharge hose and fittings, including hose check valve connected between container valve and fixed pipework manifold arrangement
pilot and slave tubes.
Finalised design documentation may include:
finalised design documentation that meets the requirements of AS 4214 or equivalent that may include information about:
manufacturers’ information
material safety data sheets on agents and equipment
system concentration and calculations
technical bulletins.
Installation drawings may include:
installation drawings that meet the requirements of AS 4214 or equivalent and may include information about:
‘for construction’ drawings
‘as installed’ or ‘as built’ drawings.
Pre-tested or prefabricated components may include:
container with valve assembly
flexible discharge hose with fittings.
Acceptable condition may include:
use of safety devices
use of transport caps.
Tools, equipment and materials may include:
hand tools, including:
hammers
nail guns
pliers
screwdrivers
spanners
spirit levels
manual-handling aids, including:
hand trucks
hooks
lifting magnets and straps
suction grips
trolleys
wheelbarrows
power tools, including:
battery powered drills
hammer drills
servicing tools and equipment, including:
hydrostatic test equipment
recharging and pressurising equipment
safety equipment
scales
service tag punch
fire equipment spare parts, including:
anti-tamper seals
hoses
labels
nozzles
pressure indicators
seals
service tags
valves
non-licensed mechanical-handling aids, including:
cranes
hoists
manually-operated forklifts and pallet trucks.
Hardware components may include:
actuators
agent discharge nozzles
agent distribution pipework and hoses
bolts and nuts
container valves
control equipment
double-sided tape
extinguishing agent containers, such as tanks and cylinders
hex nipples
identifying signs
liquid adhesives
nails
pipe adaptor bush fittings
plugs
pneumatic detection devices
screws
support brackets
thread sealant.
Work permits may include permits to:
enter a work site
enter a restricted area within a work site
enter a work site at specific times
ensure that specific OHS requirements are met before entering a work site.
Safety procedures may include:
confirmed acceptable floor loading
container handing techniques
job safety analysis (JSA) performed for installation, in particular, manual handling.
Customer requirements may include:
confirming installation instructions
confirming variations to installation instructions
following sign-in and sign-out procedures for entry to or exit from premises
providing non-routine or urgent services
providing routine services
sighting work permits
written or verbal confirmation of services provided and future services, such as maintenance.
Hazards may include:
environmental, including:
improper use of hazardous material and other chemicals
improper use or emission of ODS and SGG; emissions may be caused by:
transporting, storing and manual handling containers containing ODS and SGG agents
servicing and maintaining container valve assemblies
installing and removing container valve assembly, manifold connection components and activating mechanisms
conducting interface tests during commissioning, servicing and decommissioning procedures between container activating mechanisms, control and indicating equipment (CIE) and fire alarm systems
ergonomic, such as incorrect manual-handling methods
any source of potential harm
equipment in a work site
hazards associated with electrical or mechanical faults
obstructive, such as blocked access to emergency entry or exit points
people in a work site
work methods, plans and procedures.
Actuators (also known as actuation control devices) may include:
electrical operation: signal generated from the CIE panel as part of a fire alarm detection system
manual operation: by direct push lever or pull cable system
mechanical operation
pneumatic operation.
Auxiliary shutdown fire system and equipment:
may include:
auxiliary shutdown valves that interrupt fuel or electricity supplies before the extinguishing agent is discharged
may interact with:
air conditioning equipment
fire dampers
lock-out switches for gas extraction.
Documentation may include:
corrective action reports
customer recommendation forms
equipment recommendation forms
expense claims
job cards
maintenance record systems
manufacturers’ system documentation
product documentation
service agreements
test results and test reports.
The evidence guide provides advice on assessment and must be read in conjunction with the performance criteria, required skills and knowledge, range statement and the Assessment Guidelines for the Training Package.
Overview of assessment
This unit of competency could be assessed by observation of practical demonstration of the installation of gaseous agent containers and actuators in customers’ premises or simulated workplace.
Critical aspects for assessment and evidence required to demonstrate competency in this unit
A person who demonstrates competency in this unit must be able to provide evidence of the required skills and knowledge specified in this unit.
In particular the person should demonstrate the ability to:
communicate and work effectively and safely with others
comply with organisational policies and procedures, including quality requirements
comply with site safety plan, OHS regulations and ODS and SGG regulations (where required) and state and territory legislation applicable to workplace operations
install gaseous agent containers and actuators in a minimum of two different settings, including:
identifying risk reduction measures
identifying, selecting and assembling hardware and components
identifying, selecting and using tools, equipment and materials effectively to perform installation procedures on gaseous agent containers and actuators
checking procurement details and specifications of gaseous agent containers, actuators and materials
applying quality control checks to gaseous agent containers, actuators and materials
adhering to safety procedures during installation procedures
installing system components, fittings, actuators, activating mechanisms and auxiliary shutdown interface as required by installation guidelines
completing workplace housekeeping requirements
creating records and documentation
locate, interpret and apply relevant information, standards and specifications.
Context of and specific resources for assessment
Assessment of essential underpinning knowledge may be conducted in an off-site context. It is to comply with relevant regulatory or Australian standards’ requirements.
Resource implications for assessment include:
actual or simulated work environment, including gaseous agent containers and actuators
finalised design documentation and installation drawings for a gaseous fire-suppression system
assessment documentation, including training and assessment record books
necessary tools, specialist equipment, materials and spare parts
relevant manuals and other documentation, including Australian standards.
Method of assessment
Assessment methods must:
satisfy the endorsed Assessment Guidelines of the Property Services Training Package
include direct observation of tasks in real or simulated work conditions, with questioning to confirm the ability to consistently identify and correctly interpret the essential underpinning knowledge required for practical application
reinforce the integration of employability skills with workplace tasks and job roles
confirm that competency is verified and able to be transferred to other circumstances and environments.
Guidance information for assessment
Reasonable adjustments for people with disabilities must be made to assessment processes where required. This could include access to modified equipment and other physical resources, and the provision of appropriate assessment support.
Assessment processes and techniques should as far as is practical take into account the language, literacy and numeracy capacity of the candidate in relation to the competency being assessed.
This unit could be assessed on its own or in combination with other units relevant to the job function.