Whilst all efforts are made to provide accurate and timely information from the relevant source/documentation, please be aware that the information supplied may not be the most current version. The accuracy of the detail has not been confirmed by the Department and therefore should not be relied upon without first confirming the contents.

Disconnect - reconnect electrical equipment connected to low voltage (LV) installation wiring

Disconnect - reconnect electrical equipment connected to low voltage (LV) installation wiring

Unit of competency
National Code
UEERL0004
State Code
OCC58
TGA Status
Current
DTWD Status
Approved
Current Release Number
1.00
Current Release Date
05/10/2020
State Implementation and Classification
Approved Date
12/07/2021
Field of Education
031315 - Refrigeration And Air Conditioning Mechanics
Original Release Date
12/07/2021
Nominal Hours
54
Description
This unit involves the skills and knowledge required to disconnect and reconnect electrical equipment connected to low voltage (LV) installation wiring.It includes preparing electrical equipment for disconnecting and then reconnecting equipment connected to LV installation wiring. It also includes inspecting and testing the reconnected electrical equipment for safe operation, identifying and reporting electrical faults and providing status reports. This must be incidental to a primary or regular function of the workplace.The unit excludes disconnecting or reconnecting circuits at a switchboard or to general electrical accessories (including switches, socket outlets and circuit protective devices), or installation of or alteration to any part of the fixed electrical wiring system (defined as electrical installation work).The skills and knowledge described in this unit require a licence or permit to practice in the workplace where work is carried out on electrical installations which are designed to operate at voltages greater than 50 volt (V) alternating current (a.c.) or 120 V direct current (d.c.).The skills and knowledge described in this unit may require a license to practice in the workplace where plant and equipment operate at voltage above 50 V a.c. or 120 V d.c. However other conditions may apply in some jurisdictions subject to regulations related to electrical work. Practice in the workplace and during training is also subject to regulations directly related to occupational health and safety and where applicable contracts of training such as apprenticeships.Additional and/or other conditions may also apply under State and Territory legislation and regulations related to licencing, electrical work and work health and safety (WHS)/occupational health and safety (OHS) regulations, which must be confirmed prior to commencing this unit.In some jurisdictions additional information related to licencing may be required on certification documentation. Further guidance can be found in the UEE Electrotechnology Training Package Companion Volume Implementation Guide.
Notes
Elements and Performance Criteria
1 Prepare to disconnect electrical equipment
  • 1.1 Electrical equipment disconnection is planned to ensure WHS/OHS policies and procedures are followed
  • 1.2 Relevant person/s is consulted to ensure work is coordinated effectively with others involved at the worksite
  • 1.3 Safety hazards which have not previously been identified are documented, risks assessed, and control measures determined and implemented in consultation with relevant person/s and in accordance with workplace procedures
  • 1.4 Point of isolation of electrical equipment to be disconnected is determined
  • 1.5 Tools, equipment and testing devices needed to carry out electrical work are obtained in accordance with workplace procedures and checked for correct operation and safety
2 Disconnect electrical equipment
  • 2.1 WHS/OHS policies and workplace procedures are followed
  • 2.2 Electrical equipment is isolated in accordance with relevant electrical installation industry standards and workplace procedures
  • 2.3 Isolated equipment is confirmed as de-energised
  • 2.4 Conductor connection sequence is recorded and labelled in accordance with workplace procedures
  • 2.5 Visual inspection and checks of the electrical equipment and associated wiring are carried out in accordance with workplace procedures to detect any abnormal or obvious damage or fault
  • 2.6 Electrical equipment is disconnected from fixed wiring without damage to other components
  • 2.7 Disconnected conductors/cables are terminated in accordance with relevant industry standards to ensure they are safe and present no potential hazard
  • 2.8 Approval is obtained in accordance with workplace procedures from relevant person/s before any contingencies are implemented
3 Prepare to reconnect electrical equipment
  • 3.1 Reconnection is planned to ensure WHS/OHS policies and workplace procedures are followed
  • 3.2 Relevant person/s is consulted to ensure work is coordinated effectively with others involved in the work site
  • 3.3 Point of isolation of the circuit to which the electrical equipment to be connected is determined
  • 3.4 Replacement electrical equipment is selected on the basis of rating and specifications being the same as that of the original electrical equipment
  • 3.5 Appropriate person/s is consulted in the event that replacement electrical equipment is not available
  • 3.6 Original and/or replacement electrical equipment is inspected and tested to ensure it is safe to connect to the electrical supply and use
  • 3.7 Tools, equipment and testing devices needed to carry out electrical work, are obtained in accordance with workplace procedures and checked for correct operation and safety
4 Reconnect electrical equipment
  • 4.1 WHS/OHS policies and procedures are followed
  • 4.2 Measures are taken to ensure circuit to which electrical equipment is to be connected remains isolated and de-energised in accordance with relevant electrical installation industry standards and workplace procedures
  • 4.3 Earth continuity of the equipment is tested to determine whether it is in accordance with relevant industry standards
  • 4.4 Insulation resistance of the equipment is tested to confirm that it is in accordance with relevant industry standards
  • 4.5 Appropriate person/s is consulted regarding any non-compliant conditions identified during testing
  • 4.6 Electrical equipment is connected in accordance with previously recorded conductor connection sequence and relevant industry standards
  • 4.7 Connections to the equipment are checked to confirm they are correct
  • 4.8 Continuity between exposed conductive parts of the equipment and the main earth or metal switchboard enclosure is confirmed
5 Test the reconnected electrical equipment for safe operation
  • 5.1 WHS/OHS policies and workplace procedures for the reinstatement of isolated circuits and electrical equipment is followed
  • 5.2 Supply is reinstated to equipment and checked in accordance with established procedures and industry requirements
  • 5.3 Arrangements are made with relevant person/s to test the operation of the electrical equipment in accordance with workplace procedures
  • 5.4 Operational non-conformances are identified and reported in accordance with workplace procedures
6 Complete compliance documentation
  • 6.1 Equipment status report/s are completed and relevant person/s notified in accordance with task requirements and workplace procedures
  • 6.2 Complete compliance documentation in accordance with industry standards and regulatory requirements
No information
No information
No information
State Code National Code Title Type
BMB7 UEE32225 Certificate III in Air Conditioning and Refrigeration Qualification
BFJ5 UEE32220 Certificate III in Air Conditioning and Refrigeration Qualification
BFQ1 UEE62520 Advanced Diploma of Air Conditioning and Refrigeration Engineering Qualification
BFK7 UEE51220 Diploma of Air Conditioning and Refrigeration Engineering Qualification
BMB0 UEE51225 Diploma of Air Conditioning and Refrigeration Engineering Qualification
BMB1 UEE62525 Advanced Diploma of Air Conditioning and Refrigeration Engineering Qualification
BFP9 UEE42720 Certificate IV in Air Conditioning and Refrigeration Servicing Qualification
BMB5 UEE42725 Certificate IV in Air Conditioning and Refrigeration Servicing Qualification
BMB9 UEE42825 Certificate IV in Air-conditioning Systems Energy Management and Control Qualification
BFL0 UEE42820 Certificate IV in Air-conditioning Systems Energy Management and Control Qualification
BNZ5 UEE32125 Certificate III in Appliance Service Qualification
BFL2 UEE32120 Certificate III in Appliance Service Qualification
BFO5 UEE33020 Certificate III in Electrical Fitting Qualification
BFP8 UEE30620 Certificate III in Electrical Machine Repair Qualification
BOB0 UEE30625 Certificate III in Electrical Machine Repair Qualification
BFO7 UEE30920 Certificate III in Electronics and Communications Qualification
BNY5 UEE31025 Certificate III in Fire Protection Control Qualification
BFO4 UEE31020 Certificate III in Fire Protection Control Qualification
AE479 TLISS00209 Fuel Storage and Dispensing System Maintenance Skill Set Skill set
BGB7 CPC32720 Certificate III in Gas Fitting Qualification
BFQ5 UEE31220 Certificate III in Instrumentation and Control Qualification
BFP2 UEE42220 Certificate IV in Instrumentation and Control Qualification
BOA2 UEE31225 Certificate III in Instrumentation and Control Qualification
BHC7 UEE61521 Advanced Diploma of Instrumentation and Control Engineering Qualification
BFK6 UEE51020 Diploma of Instrumentation and Control Engineering Qualification
BGC7 CPC40920 Certificate IV in Plumbing and Services Qualification
BFN6 UEE42920 Certificate IV in Refrigeration and Air Conditioning Systems Qualification
BMB6 UEE42925 Certificate IV in Refrigeration and Air Conditioning Systems Qualification
AE264 UEESS00133 Restricted - Disconnection/Reconnection of Fixed Wired Low Voltage Electrical Equipment Skill set
BNY7 UEE30725 Certificate III in Switchgear and Controlgear Qualification
BFJ0 UEE30720 Certificate III in Switchgear and Controlgear Qualification