Whilst all efforts are made to provide accurate and timely information from the relevant source/documentation, please be aware that the information supplied may not be the most current version. The accuracy of the detail has not been confirmed by the Department and therefore should not be relied upon without first confirming the contents.

Lay wiring/cabling and terminate accessories for extra-low voltage circuits

Lay wiring/cabling and terminate accessories for extra-low voltage circuits

Unit of competency
National Code
UEENEEE008B
State Code
W7810
TGA Status
Replaced
DTWD Status
Replaced
Current Release Number
1.00
Current Release Date
24/04/2006
State Implementation and Classification
Approved Date
24/09/2012
Field of Education
031313 - Electrical Fitting, Electrical Mechanics
Original Release Date
24/09/2012
Nominal Hours
36
Description
1)1.1) DescriptorThis unit covers the laying of wiring/cabling, connection of accessories and continuity and insulation resistance testing of circuits intended to operate at extra-low voltage. Typically this includes circuits and accessories for ELV powered devices, security, controls, integrated systems, audio/video systems. It encompasses the principles of single source, single load power circuits, control circuits and communications circuits, safe working practices and following work processes that satisfy electrical principles for safety and functionality.
Notes
Elements and Performance Criteria
1 Prepare to lay wiring/cabling and connect accessories for extra-low voltage circuits.
  • 1.1 OHS procedures for a given work area are obtained and understood through established routines.
  • 1.2 Established OHS risk control measures in preparation for the work are followed.
  • 1.3 Safety hazards not previously identified are reported and advice on risk control measures is sought from the work supervisor.
  • 1.4 The nature and location of the work is obtained from work supervisor or other appropriate person to establish the scope of work to be undertaken.
  • 1.5 Advice is sought from the work supervisor or other appropriate person to ensure the work is coordinated effectively with others.
  • 1.6 Sources of materials that may be required for the work are established in accordance with established routines.
  • 1.7 Tools, equipment and testing devices needed to carry out the work are obtained and checked for correct operation and safety.
2 Lay wiring/cabling and connect accessories for extra-low voltage circuits.
  • 2.1 Established OHS risk control measures for carrying out the work are followed.
  • 2.2 Circuits/machines/plant are checked as being isolated where necessary in strict accordance OHS requirements and procedures.
  • 2.3 Wiring and accessories are installed to comply standards and job specifications with sufficient excess to affect terminations.
  • 2.4 Accessories are installed straight and square in the required locations and within acceptable tolerances.
  • 2.5 Cables and conductors are terminated at accessories in accordance with manufacture's specifications and regulatory requirements.
  • 2.6 Cables installed for future service and marked in accordance with the cable identification scheme and terminated incompliance with regulatory requirements.
  • 2.7 Procedures for referring non-routine events to immediate supervisor for directions are followed.
  • 2.8 Cable installation and termination is carried out efficiently without waste of materials or damage to apparatus, circuits or the surrounding environment and using sustainable energy practices.
3 Complete and report work activities.
  • 3.1 OHS work completion risk control measures and procedures are followed.
  • 3.2 Work site is cleaned and made safe in accordance with established procedures.
  • 3.3 Work supervisor is notified of the completion of the installation work in accordance with established routines.
RANGE STATEMENT
8) This relates to the unit as a whole providing the range of contexts and conditions to which the performance criteria apply. It allows for different work environments and situations that will affect performance.
This unit shall be demonstrated in relation to laying wiring/cabling and connecting accessories for extra-low voltage power and control cabling systems circuits using:

At least one of the following wiring/cabling systems:

Unenclosed thermoplastic sheathed (TPS) cable
Enclosed thermoplastic insulated (TPI) or sheathed cables, and

At least three of the following wiring/cabling systems:

single cable,
flexible cable,
flexible cord,
shielded cable,
armoured cable,
ribbon cable,
other similar and like cable
Generic terms used throughout this Vocational Standard shall be regarded as part of the Range Statement in which competency is demonstrated. The definition of these and other terms that apply are given in Volume 2, Part 2.1.
EVIDENCE GUIDE
9) The evidence guide provides advice on assessment and must be read in conjunction with the Performance Criteria, Required Skills and Knowledge, the Range Statement and the Assessment Guidelines for this Training Package.
The Evidence Guide forms an integral part of this unit. It must be used in conjunction with all parts of the unit and performed in accordance with the Assessment Guidelines of this Training Package.
Overview of Assessment
9.1)
Longitudinal competency development approaches to assessment, such as Profiling, require data to be reliably gathered in a form that can be consistently interpreted over time. This approach is best utilised in Apprenticeship programs and reduces assessment intervention. It is the industry-preferred model for apprenticeships. However, where summative (or final) assessment is used it is to include the application of the competency in the normal work environment or, at a minimum, the application of the competency in a realistically simulated work environment. It is recognised that, in some circumstances, assessment in part or full can occur outside the workplace. However, it must be in accordance with industry and regulatory policy.
Methods chosen for a particular assessment will be influenced by various factors. These include the extent of the assessment, the most effective locations for the assessment activities to take place, access to physical resources, additional safety measures that may be required and the critical nature of the competencies being assessed.
The critical safety nature of working with electricity, electrical equipment, gas or any other hazardous substance/material carries risk in deeming a person competent. Sources of evidence need to be 'rich' in nature to minimise error in judgment.
Activities associated with normal everyday work have a bearing on the decision as to how much and how detailed the data gathered will contribute to its 'richness'. Some skills are more critical to safety and operational requirements while the same skills may be more or less frequently practised. These points are raised for the assessors to consider when choosing an assessment method and developing assessment instruments. Sample assessment instruments are included for Assessors in the Assessment Guidelines of this Training Package.
Critical aspects of evidence required to demonstrate competency in this unit
9.2)
Before the critical aspects of evidence are considered all prerequisites must be met.
Evidence for competence in this unit shall be considered holistically. Each element and associated performance criteria shall be demonstrated on at least two occasions in accordance with the 'Assessment Guidelines - UEE07'. Evidence shall also comprise:
A representative body of work performance demonstrated within the timeframes typically expected of the discipline, work function and industrial environment. In particular this shall incorporate evidence that shows a candidate is able to:

Implement Occupational Health and Safety workplace procedures and practices, including the use of risk control measures as specified in the performance criteria and range statement
Apply sustainable energy principles and practices as specified in the performance criteria and range statement
Demonstrate an understanding of the essential knowledge and associated skills as described in this unit. It may be required by some jurisdictions that RTOs provide a percentile graded result for the purpose of regulatory or licensing requirements.
Demonstrate an appropriate level of skills enabling employment
Conduct work observing the relevant Anti Discrimination legislation, regulations, polices and workplace procedures

Demonstrated consistent performance across a representative range of contexts from the prescribed items below:

Lay wiring/cabling and terminate accessories for extra-low voltage in power and control circuits as described in 8) and including:


A
Understanding the nature of the work.


B
Selecting appropriate tools, cables and accessories.


C
Following appropriate cable routes.


D
Installing cable and accessories to requirements.


E
Terminating cables and accessories to manufacture's specifications and requirements.


F
Cleaning worksite.


G
Notifying completion of work using established procedures.
Context of and specific resources for assessment
9.3)
This unit should be assessed as it relates to normal work practice using procedures, information and resources typical of a workplace. This should include:
OHS policy and work procedures and instructions.
Suitable work environment, facilities, equipment and materials to undertake actual work as prescribed in this unit.
These should be used in the formal learning/assessment environment.
Note:
Where simulation is considered a suitable strategy for assessment, conditions for assessment must be authentic and as far as possible reproduce and replicate the workplace and be consistent with the approved industry simulation policy.

The resources used for assessment should reflect current industry practices in relation to laying wiring/cabling and terminate accessories for extra-low voltage circuits.
Method of assessment
9.4)
This unit shall be assessed by methods given in Volume 1, Part 3 'Assessment Guidelines'.
Note: Competent performance with inherent safe working practices is expected in the Industry to which this unit applies. This requires that the specified essential knowledge and associated skills are assessed in a structured environment which is primarily intended for learning/assessment and incorporates all necessary equipment and facilities for learners to develop and demonstrate the essential knowledge and skills described in this unit.
Concurrent assessment and relationship with other units
9.5)
For optimisation of training and assessment effort, competency development in this unit may be arranged concurrently with unit:
UEENEEE002B
Dismantle, assemble and fabricate electrotechnology components

UEENEEE005B
Fix and secure equipment

UEENEEE007B
Use drawings, diagrams, schedules and manuals
Replaces
State Code National Code Title Type
W6052 UEENEEE008A Lay wiring/cabling and terminate accessories for extra-low voltage circuits Unit of competency
Replaced By
State Code National Code Title Type
WC420 UEENEEE108A Lay wiring/cabling and terminate accessories for extra-low voltage (ELV) circuits Unit of competency
State Code National Code Title Type
W414 UEE21207 Certificate II in Antennae Equipment Qualification
W827 UEE30310 Certificate III in Custom Electronics Installations Qualification
W426 UEE30307 Certificate III in Custom Electronics Installations Qualification
W410 UEE20707 Certificate II in Data and Voice Communications Qualification
W427 UEE30407 Certificate III in Data and Voice Communications Qualification
W839 UEE40410 Certificate IV in Electrical - Instrumentation Qualification
W853 UEE42010 Certificate IV in Electrical - Photovoltaic Systems Qualification
W852 UEE41910 Certificate IV in Electrical - Renewable Energy Qualification
W870 UEE60110 Advanced Diploma of Electrical Engineering Qualification
W471 UEE60107 Advanced Diploma of Electrical Engineering Qualification
W863 UEE50410 Diploma of Electrical Engineering Qualification
W841 UEE40610 Certificate IV in Electrotechnology - Systems Electrician Qualification
W431 UEE30807 Certificate III in Electrotechnology Electrician Qualification
5671 51908 Certificate I in Electrotechnology Pre-Apprentice Electrical Accredited course
W884 UEE62110 Advanced Diploma of Engineering Technology - Electrical Qualification
W412 UEE21007 Certificate II in Fire Alarms Servicing Qualification
W433 UEE31007 Certificate III in Fire Protection Control Qualification
W859 UEE42610 Certificate IV in Hazardous areas - Electrical Qualification
W439 UEE31707 Certificate III in Hazardous areas - Electrician Qualification
W832 UEE31710 Certificate III in Hazardous areas - Electrician Qualification
W844 UEE40910 Certificate IV in Industrial Electronics and Control Qualification
W873 UEE60610 Advanced Diploma of Industrial Electronics and Control Engineering Qualification
W415 UEE21307 Certificate II in Remote Area Essential Service Qualification
W850 UEE41610 Certificate IV in Renewable Energy Qualification
W417 UEE21507 Certificate II in Renewable Energy Qualification
W824 UEE21510 Certificate II in Renewable Energy Qualification
W835 UEE32010 Certificate III in Renewable Energy - ELV Qualification
W442 UEE32007 Certificate III in Renewable Energy ELV Qualification
W418 UEE21607 Certificate II in Security Assembly and Setup Qualification
W437 UEE31407 Certificate III in Security Equipment Qualification
W831 UEE31410 Certificate III in Security Equipment Qualification