Whilst all efforts are made to provide accurate and timely information from the relevant source/documentation, please be aware that the information supplied may not be the most current version. The accuracy of the detail has not been confirmed by the Department and therefore should not be relied upon without first confirming the contents.

Install low voltage wiring and accessories

Install low voltage wiring and accessories

Unit of competency
National Code
UEENEEG103A
State Code
S7320
TGA Status
Deleted
DTWD Status
Deleted
Current Release Number
3.00
Current Release Date
14/08/2013
State Implementation and Classification
Approved Date
29/10/2014
Field of Education
031313 - Electrical Fitting, Electrical Mechanics
Original Release Date
29/10/2014
Nominal Hours
18
Description
1) 1.1) DescriptorThis unit covers the installation in building and premises of wiring enclosures, cable support systems, cables and accessories and designed to operate at voltages up to 1,000 V a.c. or 1,500 V d.c. It encompasses working safely and to installation standards, routing cables to specified locations, terminating cables and connecting wiring at accessories and completing the necessary installation documentation.
Notes
Elements and Performance Criteria
1 Prepare to install wiring and accessories.
  • 1.1 OHS procedures for a given work area are identified, obtained and understood.
  • 1.2 Health and safety risks are identified and established risk control measures and procedures in preparation for the work are followed.
  • 1.3 Safety hazards that have not previously been identified are noted and established risk control measures are implemented.
  • 1.4 Installation of wiring is prepared in consultation with other affected by the work and sequenced appropriately.
  • 1.5 The nature and location of the work is determined from documentation or other appropriate person to establish the scope of work to be undertaken.
  • 1.6 Cable routes are planned within the constraints of the building structure, significants and requirements.
  • 1.7 Material needed for the installation work is obtained in accordance with established procedures and checked against job requirements.
  • 1.8 Tools, equipment and testing devices needed to for the installation work are obtained in accordance with established procedures and checked for correct operation and safety.
  • 1.9 Preparatory work is checked to ensure no damage has occurred and complies with requirements.
2 Install wiring and accessories.
  • 2.1 OHS risk control measures and procedures for carrying out the work are followed.
  • 2.2 The need to test or measure live is determined in strict accordance with OHS requirements and when necessary conducted within established safety procedures.
  • 2.3 Circuits/machines/plant are checked as being isolated where necessary in strict accordance OHS requirements and procedures.
  • 2.4 Wiring and accessories are installed to comply with technical standards and job specifications and requirements with sufficient excess to affect terminations.
  • 2.5 Accessories are installed straight and square in the required locations and within acceptable tolerances.
  • 2.6 Cables and conductors are terminated at accessories in accordance with manufacture's specifications and regulatory requirements.
  • 2.7 Ongoing compliance and safety inspection of installed wiring systems and testing of installed circuits is undertaken.
  • 2.8 Defects revealed through on-going compliance and safety inspection and tests are rectified.
  • 2.9 Cable installation and termination is carried out efficiently without unnecessary waste of materials or damage to apparatus, circuits or the surrounding environment and using sustainable energy practices.
  • 2.10 Unexpected situations are dealt with safely and with the approval of an authorised person.
3 Completion and report installation activities.
  • 3.1 OHS work completion risk control measures and procedures are followed.
  • 3.2 Work site is cleaned and made safe in accordance with established procedures.
  • 3.3 'As-installed' cables/wiring and accessories is documented and an appropriate person or persons notified in accordance with established procedures.
RANGE STATEMENT
8) This relates to the unit as a whole providing the range of contexts and conditions to which the performance criteria apply. It allows for different work environments and situations that will affect performance.
This unit shall be demonstrated in relation to at least three different types of cable enclosure/support systems in combination with four different cable types and circuits for five different purposes as listed below.
Wiring systems enclosures and supports:
Metallic conduit
Non-metallic conduit
Trunking
Duct
Cable tray/ladder
Catenary
Posts/poles/struts
Cable types:
Thermoplastic insulated cable (TPI)
Flat thermoplastic sheathed (TPS)
Circular thermoplastic sheathed (TPS)
Steel wire armoured (SWA)
Fire rated cable ( HT or HF or MIMS)
Flexible cables
Aerial cable
Circuit purpose:
Consumers mains
Submains
Alternative supply
Lighting;
Socket outlets
Single phase fixed appliance
Single phase motor
Three phase motor
Control
Generic terms used throughout this Vocational Standard shall be regarded as part of the Range Statement in which competency is demonstrated. The definition of these and other terms that apply are given in Volume 2, Part 2.1.
EVIDENCE GUIDE
9) The evidence guide provides advice on assessment and must be read in conjunction with the Performance Criteria, Required Skills and Knowledge, the Range Statement and the Assessment Guidelines for this Training Package.
The Evidence Guide forms an integral part of this unit. It must be used in conjunction with all parts of this unit and performed in accordance with the Assessment Guidelines of this Training Package.
Overview of Assessment
9.1)
Longitudinal competency development approaches to assessment, such as Profiling, require data to be reliably gathered in a form that can be consistently interpreted over time. This approach is best utilised in Apprenticeship programs and reduces assessment intervention. It is the Industry's preferred model for apprenticeships. However, where summative (or final) assessment is used it is to include the application of the competency in the normal work environment or, at a minimum, the application of the competency in a realistically simulated work environment. It is recognised that, in some circumstances, assessment in part or full can occur outside the workplace. However, it must be in accordance with industry and regulatory policy.
Methods chosen for a particular assessment will be influenced by various factors. These include the extent of the assessment, the most effective locations for the assessment activities to take place, access to physical resources, additional safety measures that may be required and the critical nature of the competencies being assessed.
The critical safety nature of working with electricity, electrical equipment, gas or any other hazardous substance/material carries risk in deeming a person competent. Sources of evidence need to be 'rich' in nature to minimise error in judgment.
Activities associated with normal every day work have a bearing on the decision as to how much and how detailed the data gathered will contribute to its 'richness'. Some skills are more critical to safety and operational requirements while the same skills may be more or less frequently practised. These points are raised for the assessors to consider when choosing an assessment method and developing assessment instruments. Sample assessment instruments are included for Assessors in the Assessment Guidelines of this Training Package.
Critical aspects of evidence required to demonstrate competency in this unit
9.2)
Before the critical aspects of evidence are considered all prerequisites shall be met.
Evidence for competence in this unit shall be considered holistically. Each element and associated performance criteria shall be demonstrated on at least two occasions in accordance with the 'Assessment Guidelines - UEE07'. Evidence shall also comprise:
A representative body of work performance demonstrated within the timeframes typically expected of the discipline, work function and industrial environment. In particular this shall incorporate evidence that shows a candidate is able to:

Implement Occupational Health and Safety workplace procedures and practices including the use of risk control measures as specified in the performance criteria and range statement
Apply sustainable energy principles and practices as specified in the performance criteria and range statement
Demonstrate an understanding of the essential knowledge and associated skills as described in this unit. It may be required by some jurisdictions that RTOs provide a percentile graded result for the purpose of regulatory or licensing requirements.
Demonstrate an appropriate level of skills enabling employment
Conduct work observing the relevant Anti Discrimination legislation, regulations, polices and workplace procedures

Demonstrated consistent performance across a representative range of contexts from the prescribed items below:

Install wiring and accessories for low voltage circuits as described as described in 8) and including:


A
Reading and interpreting drawings related to cable layouts, cable schedules and apparatus locations.


B
Planning cable routes and obtaining installation materials.


C
Sequencing the installation effectively with other affected by the work.


D
Routing, placing and securing cables in compliance with requirements.


E
Placing and securing accessories accurately.


F
Maintaining fire integrity.


G
Terminating cable and conductors to comply with requirements.


H
Undertaking on-going compliance and safety inspection and testing of installed circuits.


I
Rectifying any defects revealed through on-going inspection and testing


J
Correctly documenting 'as-installed' cables/wiring and accessories.


K
Dealing with unplanned events
Context of and specific resources for assessment
9.3)
This unit should be assessed as it relates to normal work practice using procedures, information and resources typical of a workplace. This should include:
OHS policy and work procedures and instructions.
Suitable work environment, facilities, equipment and materials to undertake actual work as prescribed by this unit.
These should be part of the formal learning/assessment environment.
Note:
Where simulation is considered a suitable strategy for assessment, conditions must be authentic and as far as possible reproduce and replicate the workplace and be consistent with the approved industry simulation policy.

The resources used for assessment should reflect current industry practices in relation to installing wiring and accessories for low voltage circuits.
Method of assessment
9.4)
This unit shall be assessed by methods given in Volume 1, Part 3 'Assessment Guidelines'.
Note: Competent performance with inherent safe working practices is expected in the industry to which this unit applies. This requires assessment in a structured environment which is primarily intended for learning/assessment and incorporates all necessary equipment and facilities for learners to develop and demonstrate the essential knowledge and skills described in this unit.
Concurrent assessment and relationship with other units
9.5)
For optimisation of training and assessment effort, competency development in this unit may be arranged concurrently with unit:
UEENEEG104A
Install appliances, switchgear and associated accessories for low voltage electrical installations
Replaces
State Code National Code Title Type
W7882 UEENEEG003B Install wiring and accessories for low voltage circuits Unit of competency
State Code National Code Title Type
A136 UEE40511 Certificate IV in Electrical - Air-conditioning Split Systems Qualification
A133 UEE40211 Certificate IV in Electrical - Data and Voice Communications Qualification
D642 UEE62211 Advanced Diploma of Electrical - Engineering Qualification
A139 UEE40811 Certificate IV in Electrical - Fire Protection Control Systems Qualification
A135 UEE40411 Certificate IV in Electrical - Instrumentation Qualification
A142 UEE41111 Certificate IV in Electrical - Lift Systems Qualification
A149 UEE42011 Certificate IV in Electrical - Photovoltaic systems Qualification
A143 UEE41211 Certificate IV in Electrical - Rail Signalling Qualification
A147 UEE41911 Certificate IV in Electrical - Renewable Energy Qualification
A156 UEE50211 Diploma of Electrical and Instrumentation Qualification
A157 UEE50311 Diploma of Electrical and Refrigeration and Air-conditioning Qualification
A158 UEE50411 Diploma of Electrical Engineering Qualification
A148 UEE42111 Certificate IV in Electrotechnology - Electrical Contracting Qualification
A138 UEE40611 Certificate IV in Electrotechnology - Systems Electrician Qualification
A123 UEE30811 Certificate III in Electrotechnology Electrician Qualification
A153 UEE43111 Certificate IV in Energy Efficiency and Assessment Qualification
A141 UEE41011 Certificate IV in Energy Management and Control Qualification
A170 UEE61211 Advanced Diploma of Engineering - Explosion protection Qualification
J169 UET40612 Certificate IV in ESI - Power Systems Network Infrastructure Qualification
BHB1 UET40621 Certificate IV in ESI - Power Systems Network Infrastructure Qualification
BEV3 UET40619 Certificate IV in ESI - Power Systems Network Infrastructure Qualification
BHB2 UET40521 Certificate IV in ESI - Power Systems Substations Qualification
J168 UET40512 Certificate IV in ESI - Power Systems Substations Qualification
BEV5 UET40519 Certificate IV in ESI - Power Systems Substations Qualification
A151 UEE42611 Certificate IV in Hazardous areas - Electrical Qualification
A140 UEE40911 Certificate IV in Industrial Electronics and Control Qualification
A162 UEE50911 Diploma of Industrial Electronics and Control Engineering Qualification
A167 UEE60611 Advanced Diploma of Industrial Electronics and Control Engineering Qualification
A134 UEE40311 Certificate IV in Installation Inspection and Audits Qualification
A159 UEE50711 Diploma of Renewable Energy Engineering Qualification
A168 UEE60911 Advanced Diploma of Renewable Energy Engineering Qualification